Users Guide
CN9400
Dual Display Autotune Temperature Controller
omega.com
TM
OMEGA
®
OMEGAnet
SM
On-Line Service Internet e-mail
http://www.omega.com [email protected]
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New
Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter
specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
Benelux:
Postbus 8034, 1180 LAAmstelveen,
The Netherlands
Tel: (31) 20 6418405 FAX: (31) 20 6434643
Toll Free in Benelux: 06 0993344
Czech Republic:
ul. Rude armady 1868, 733 01 Karvina-Hranice,
Czech Republic
Tel: 420 (69) 6311899 FAX: 420 (69) 6311114
France:
9, rue Denis Papin, 78190 Trappes
Tel: (33) 130-621-400 FAX: (33) 130-699-120
Toll Free in France: 0800-4-06342
Servicing Europe:
USA and Canada:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
SM
Customer Service: 1-800-622-2378 / 1-800-622-BEST
SM
Engineering Service: 1-800-872-9436 /
1-800-USA-WHEN
SM
TELEX: 996404 EASYLINK: 62968934
CABLE: OMEGA
USA: ISO 9001 Cer
tified
One Omega Drive, Box 4047
Stamford, CT 06907-0047
Tel: (203) 359-1660
FAX: (203) 359-7700
Servicing North America:
For immediate technical or application assistance:
Mexico and Latin America:
Tel: (95) 800-TC-OMEGA
SM
FAX: (95) 203-359-7807
En Espan
~
ol: (203) 359-7803
Germany/Austria:
Daimlerstrasse 26, D-75392
Deckenpfronn, Germany
Tel: 49 (07056) 3017 FAX: 49 (07056) 8540
Toll Free in Germany: 0130 11 21 66
United Kingdom: ISO 9002 Cer
tified
25 Swannington Road, Broughton Astley,
Leicestershire, LE9 6TU, England
Tel: 44 (1455) 285520
FAX: 44 (1455) 283912
P.O. Box 7, Omega Drive, Irlam,
Manchester, M44 5EX, England
Tel: 44 (161) 777-6611
FAX: 44 (161) 777-6622
Toll Free in England: 0800-488-488
Canada:
976 Bergar
Laval (Quebec) H7L 5A1
Tel: (514) 856-6928
FAX: (514) 856-6886
M2982/0798
Seitenansicht 0
1 2 3 4 5 6 ... 37 38

Inhaltsverzeichnis

Seite 1 - User’s Guide

http://www.omega.com e-mail: [email protected]®User’s GuideCN9400Dual Display Autotune Temperature Controlleromega.comTMOMEGA®OMEGAnetSMOn-Line Service

Seite 2 - SAFETY INFORMATION

Menu NavigationMENU NAVIGATIONTo change an option value or settingPress and hold the ✱ button, then press ▲ to increase or ▼ todecrease the value or s

Seite 3

AutotuneAUTOTUNESelect the most appropriate method of Autotune , Tune orTune at Setpoint, to suit the application.Note: The proportional cycle-time ca

Seite 4 - FUNCTIONS MENU

AutotuneThe TUNE AT SETPOINT program will now start. The upper displaywill alternate tune and the process temperature.The lower display will read the

Seite 5

Proportional cycle-timeThe choice of cycle-time is influenced by the external switchingdevice or load. eg. contactor, SSR, valve. A setting that is to

Seite 6 - INTRODUCTION

If this cycle-time is suitable press and hold both ▲ and ▼buttons for 3 seconds to enter it into the controllersmemory.If the calculated cycle-time is

Seite 7 - OVERVIEW

ProgrammerRAMP-SOAKThis feature enables the controller to ramp up or down from currenttemperature to a target setpoint at a pre-determined rate. It th

Seite 8 - Overview

The second setpoint SP2 can be used to trigger an alarmor as a proportional control output.TO CONFIGURE SP2 AS AN ALARMEnter program mode.Select level

Seite 9

Second SetpointSUBSIDIARY SP2 MODE:Latch/sequence or non-linear cool. Latch alarm LtChWhen activated, the alarm latches until manually reset, eventhou

Seite 10 - MENU NAVIGATION

Error MessagesERROR MESSAGESTempSetpointCycle75% SPStartTUNETUNETuningDACPIDNew PIDvaluesenteredTime(100% output)oS 1oS 2Ct ACt bCt 3Ct 4uSCt 1Ct 2SEN

Seite 11 - AUTOTUNE

Improving Control AccuracyIMPROVING CONTROL ACCURACYTempMaximumTimeVarianceVAr°hi°±0.1°MinimumLo°The following functions are to assist engineers withm

Seite 12 - Autotune

Safety InformationSAFETY INFORMATIONINSTALLATIONDesigned for use:UL873 - only in products where the acceptability is determined byUnderwriters Laborat

Seite 13 - PROPORTIONAL CYCLE-TIME

Function ListFUNCTION LIST (Levels 1 to 4)BANDToo narrow(oscillates)increaseToo wide(slow warm up and response)decreaseBANDNote: A Functions Menu is s

Seite 14 - Proportional cycle-time

Function ListFunction Options[Factory settings] shown in bracketsA - - on.oF 0.1 - 81 sec [20]SP1 proportional cycle-time (see pages 9/10)

Seite 15 - PROGRAMMER

Function ListLEVEL 2Function Options[Factory settings] shown in bracketsMANUAL CONTROL MODES0 to 100 % ‘read only’Read SP1 output percentage

Seite 16 - SECOND SETPOINT (SP2)

Function ListSensor burn-out/break protectionCaution: Settings affect fail safe state.SP1 SP2[uP.SC]Upscale Upscaledn.SC Downscale

Seite 17 - Second Setpoint

Function ListFunction Options[Factory settings] shown in bracketsSelect SP1/2 LED indicator modesSP1 SP2[1n.2n]Normal Normal1i.2nInvert Normal1n.

Seite 18 - ERROR MESSAGES

Function ListLEVEL 4Access to level 4 is gained through in level 3.Press and hold ▲ and ▼ for 10 seconds.Enter level 4 at Lock, relea

Seite 19 - IMPROVING CONTROL ACCURACY

FACTORY SET OUTPUT OPTIONS22DUAL RELAY OR DUAL SSd OUTPUT MODELSThe table below details the factory set output options. rLY2 is a 1Aelectromechanical

Seite 20 - (Levels 1 to 4)

Advanced SettingsBefore embarking on the Advanced Settings, pleasefamiliarise yourself with the basic operation of the controlleras described in this

Seite 21 - Function List

Advanced SettingsHeat Cool Strategy Configuration (continued)If no improvement, return to the original value and;In level 1 halve the value ofIf the p

Seite 22

Advanced Settings2.5 Therefore adjust SPAnto (-) 18 to correct error.Notes: (1) After making the adjustment the reading will immediately change. All

Seite 23

Safety InformationSAFETY INFORMATIONINSTALLATIONDesigned for use:UL873 - only in products where the acceptability is determined byUnderwriters Laborat

Seite 24

Advanced Settings3 Allocate the output devices at functionas described in SET-UP, enter the configurationinto the memory and proceed as follows:Calcul

Seite 25

Mechanical InstallationThe CN9400 Controller is designed to be mounted in a 1/16 DINpanelcutout.The unit is sleeve mounted with the front bezel assemb

Seite 26 - FACTORY SET OUTPUT OPTIONS

Mechanical InstallationMINIMUM SPACINGMOUNTINGTo mount a Controller proceed as follows:1 Check that the controller is correctly orientated and then sl

Seite 27 - ADVANCED SETTINGS

Electrical InstallationOUTPUT DEVICESTwo of the following output devices are fitted to the controllers,depending on the model.1 Solid state relay driv

Seite 28 - Advanced Settings

Electrical Installation30ELECTRICAL INSTALLATION (continued)EN61010 - /CSA 22.2 No 1010.1 92Compliance shall not be impaired when fitted to the finali

Seite 29 - SPAn

Sensor SelectionOption/Sensor type Sensor range LinearityThermocouplestc b B 0 to 1800 °C 32 to 3272 F Pt-30%Rh/Pt-6%Rh 2.0 *tc E E 0 to 600 °C 32 to

Seite 30

SpecificationThermocouple9 typesStandards: IPTS/68/DIN 43710CJC rejection: 20:1 (0.05°/°C) typicalExternal resistance: 100Ω maximumResistance the

Seite 31 - MECHANICAL INSTALLATION

FOR WARRANTY RETURNS, please have the following informationavailable BEFORE contacting OMEGA:1. P.O. number under which the product was PURCHASED,2. M

Seite 32 - Mechanical Installation

http://www.omega.com e-mail: [email protected]®User’s GuideCN9400Dual Display Autotune Temperature Controlleromega.comTMOMEGA®OMEGAnetSMOn-Line Service

Seite 33 - ELECTRICAL INSTALLATION

FUNCTIONS MENUFunctions MenuINSTRUMENT ADJUSTMENTSTo enter or exit program mode: Press ▲ ▼ together for 3 secondsTo scroll through functions: Press ▲

Seite 34 - Electrical Installation

2 Select unit.Press and hold ✱ and use the ▲ or ▼ buttons to scroll through the unit selection list until the correct unit is displayed. Release the b

Seite 35 - SENSOR SELECTION

IntroductionINTRODUCTIONThe CN9400 is a 1/16 DIN dual display, dual output miniaturecontroller with PID control strategy.Control can be optimised with

Seite 36 - SPECIFICATION

OverviewOVERVIEWINSTALLATIONThe Model CN9400 controller is designed to be mounted in a 1/16DIN panel cut-out. See the INSTALLATION section.SET-UPAfter

Seite 37 - QUICK START

OverviewCYCLE-TIMEThe choice of cycle-time is influenced by the external switchingdevice or load. e.g. contactor, SSR, Valve. A setting that is too l

Seite 38

Set-upSET-UP5This section details the four step initial configuration thatenables control with factory PID settings to start, once thesetpoint has bee